Setting up the diode supply unit for fieldbus control

Before configuring the diode supply unit for fieldbus control, the adapter module
must be mechanically and electrically installed according to the instructions given in
the user's manual of the appropriate fieldbus adapter module.
Note: To be able to switch the main contactor and the supply unit on and off through
the fieldbus, the Run enable command at the digital input DI2 (by default) must be
on (1). That is the case when the operating switch [S11] is switched to the on (1)
position.
1.
Power up the diode supply unit.
2. Enable the communication between the diode supply unit and the fieldbus
adapter module by setting parameter
3. With
150.02 FBA A comm loss
to a fieldbus communication break.
Note: This function monitors both the communication between the fieldbus
master and the adapter module and the communication between the adapter
module and the diode supply unit.
4. With
150.03 FBA A comm loss t
break detection and the selected action.
5. Select application-specific values for the rest of the parameters in group
FBA.
6. Set the fieldbus adapter module configuration parameters in group
settings. At the minimum, set the required node address and the communication
profile. Set profile to transparent 16 mode.
Note: The parameter indexes and names vary as the way the different fieldbus
adapters use these parameters.
Example: For the FPBA adapter, set parameter 151.05 Profile to mode Trans16.
7.
Define the process data transferred to and from the diode supply unit in
parameter groups
Note: The adapter module sets the Status word and Control word automatically
into parameters
8. Save the valid parameter values to permanent memory by setting parameter
196.07 Parameter save manually
9. Validate the settings made in parameter groups 151, 152 and 153 by setting
parameter
151.27 FBA A par refresh
10. Select the fieldbus adapter A as the source of the start and stop commands for
external control location EXT1 by setting parameter
Fieldbus
A.
11. Set the relevant control parameters to control the diode supply unit according to
the application.
func, select how the diode supply unit should react
out, define the time between communication
152 FBA A data in
152.01
and
153.01
respectively.
to Save.
Fieldbus control through a fieldbus adapter 195
150.01 FBA A enable
and
153 FBA A data
to Refresh.
120.01 Ext1 commands
to
Option slot
1.
150
151 FBA A
out.
to