Contents of the fieldbus Status word

Bit
Name
0
Ready to
switch ON
1
Ready run
2
Ready ref
3
Tripped
4
-
5
-
6
-
7
Warning
8
Operating
9
Remote
command
10
Ready for load
11
User bit 0
12
User bit 1
13
User bit 2
14
Charging
15
User bit 3
Value
Description
1
Ready to switch ON
Note: If the supply unit is switched off, the Start enable must be
on for Ready to switch ON = 1. If the supply unit is switched on,
Ready to switch ON = 1 regardless of the Start enable.
0
Not ready to switch ON
1
Ready to operate. Start command is on and main contactor is
closed.
0
Start command is not given or main contactor is open.
1
Operation enabled
0
Operation inhibited
1
Fault
0
No fault active
1
Not in use.
0
Not in use.
1
Not in use.
0
Not in use.
1
Not in use.
0
Not in use.
1
A warning is active
0
No warnings active
1
Thyristors of the DxT module are modulating, during charging or
when the supply unit is running. During charging, thyristors are
already conducting, but DC voltage has not yet risen to 'Ready
ref' level.
0
Thyristors of the DxT module are not modulating.
1
Drive in remote mode, fieldbus control enabled.
0
Drive in local mode, Control word bits 0...7 received and executed
by drive. Control word bits 8...15 and reference 1 and 2 received
by drive but not executed.
1
Ready for load.
0
Not ready for load.
1
See parameter
0
See parameter
1
See parameter
0
See parameter
1
See parameter
0
See parameter
1
Charging state is active.
0
Charging state is not active.
1
See parameter
0
See parameter
Fieldbus control through a fieldbus adapter 193
106.30 MSW bit 11
sel.
106.30 MSW bit 11
sel.
106.31 MSW bit 12
sel.
106.31 MSW bit 12
sel.
106.32 MSW bit 13
sel.
106.32 MSW bit 13
sel.
106.33 MSW bit 15
sel.
106.33 MSW bit 15
sel.