Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
195.20
HW options word 1
Bit
Name
0...10 Reserved
11
INU-DSU
communication
12
Reserved
13
DOL fan
14
DIO1 for brake
chopper feedback
15
ACS880-307LC
0000h...FFFFh
195.30
Parallel type list
filter
All types
-3 (380-415V)
-5 (380-500V)
-7 (525-690V)
195.31
Parallel connection
rating id
Not selected
Description
Specifies hardware-related options that require
differentiated parameter defaults. Activating a bit in
this parameter makes the necessary changes in other
parameters. In many cases, the differentiated
parameters will also be write-protected.
This parameter, as well as the changes in other
parameters implemented by it, are not affected by a
parameter restore.
WARNING! After switching any bits in this word,
recheck the values of the affected parameters.
Information
Reserved
Enables DDCS communication with ACS880 inverter. Selects
DDCS controller as the control source, enables the
communication and configures required dataset parameters.
Sets parameter:
119.11 Ext1/Ext2 sel
120.01 Ext1 commands
160.51 DDCS controller comm port
160.52 DDCS controller node address
161.51 Data set 11 data 1 selection
162.51 Data set 10 data 1 selection
Reserved
Direct-on-line cooling fan is used instead of speed-controlled
cooling fan. Disables fan feedback monitoring and changes fan
control to ON/OFF type.
Sets parameter
131.39 Brake chopper fault source
DxT modules only: Sets parameter
111.05 DIO1 function
111.09 DIO2 function
131.32 Aux circuit breaker fault source
131.38 Fuse trip fault source
131.39 Brake chopper fault source
• 206.01 I/O bus enable to Yes,
• 206.50 MCB monitoring action to Fault,
• 206.51 Fuse monitoring action to No.
Hardware options configuration word.
DxT modules only: Filters the list of drive/supply unit
types listed by parameter
rating
id.
All types listed.
-3 (380...415 V) types listed.
-5 (380...500 V) types listed.
-7 (525...690 V) types listed.
DxT modules only: Defines the drive/supply unit type if
it consists of parallel-connected modules.
If the drive/supply unit consists of a single module,
leave the value at
Not
selected.
The drive/supply unit does not consist of parallel-
connected modules, or type not selected.
to EXT1,
to
DDCS
controller,
to
to
to
111.05 DIO1 function
to Input, and parameter
to DIO1.
to Input,
to Input,
to DIO2,
to DIO1,
195.31 Parallel connection
Parameters 133
Def/FbEq16
-
RDCO CH
0,
to 1,
SW
16bit,
CW
16bit.
to
Inactive
(true),
1 = 1
All types
0
1
2
3
Not selected
0