ABB ACS880 Firmware Manual page 98

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

98 Parameters
No.
Name/Value
DI6
DIO1
DIO2
FBA A MCW bit 7
FBA B MCW bit 7
Other [bit]
131.12
Autoreset
selection
Bit
Fault
0
Overcurrent
1
Overvoltage
2
Undervoltage
3...9
Reserved
10
User fault (selected by parameter
11
External fault 1 (from source selected by parameter
source)
12
External fault 2 (from source selected by parameter
source)
13
External fault 3 (from source selected by parameter
source)
14
External fault 4 (from source selected by parameter
source)
15
External fault 5 (from source selected by parameter
source)
0000h...FFFFh
131.13
User selectable
fault
0000h...FFFFh
131.14
Number of trials
0...5
Description
Digital input DI6 (as indicated by
status
bit 5).
Digital input/output DIO1 (as indicated by
delayed
status, bit 0).
Digital input/output DIO2 (as indicated by
delayed
status, bit 1).
Control word bit 7 received through fieldbus interface A. 30
Control word bit 7 received through fieldbus interface B. 31
Source selection (see
Terms and abbreviations
39).
Selects faults that are automatically reset. The
parameter is a 16-bit word with each bit corresponding
to a fault type. Whenever a bit is set to 1, the
corresponding fault is automatically reset.
Note: The autoreset function is available in external
control only.
WARNING! The supply unit starts automatically
after the autoreset if Start, Run enable and
Start enable signals are on and the control
program detects no fault. Before you activate the
function, make sure that no dangerous situations can
occur. The function resets the supply unit automatically
and continues operation after a fault. If you select an
external source for the start command and it is on, the
supply unit will start immediately after fault reset.
The bits of the binary number correspond to the
following faults:
(2E00
Overcurrent)
(3E04 DC link
overvoltage)
(3E05 DC link
undervoltage)
Automatic reset configuration word.
Defines the fault that can be automatically reset using
parameter
131.12 Autoreset
The faults are listed in chapter
Fault code. See chapter
Defines the number of automatic fault resets the supply
unit performs within the time defined by parameter
131.15 Total trials
time.
Number of automatic resets.
110.02 DI delayed
111.02 DIO
111.02 DIO
131.13 User selectable
fault)
131.01 External event 1
131.03 External event 2
131.05 External event 3
131.07 External event 4
131.09 External event 5
selection, bit 10.
Fault
tracing.
Fault
tracing.
Def/FbEq16
7
10
11
on page
-
0000h
1 = 1
0000h
-
0
-