ABB ACS880 Firmware Manual page 61

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
112.04
AI supervision
selection
Bit
Name
0
AI1 < MIN
1
AI1 > MAX
2
AI2 < MIN
3
AI2 > MAX
4...15
Reserved
0000b...1111b
112.11
AI1 actual value
-22.000 ... 22.000
mA or V
112.12
AI1 scaled value
-32768.000 ...
32767.000
112.15
AI1 unit selection
mA
V
112.16
AI1 filter time
0.000 ... 30.000 s
112.17
AI1 min
-22.000 ... 22.000
V or mA
112.18
AI1 max
-22.000 ... 22.000
V or mA
Description
Specifies the analog input limits to be supervised. See
parameter
112.03 AI supervision
Description
1 = Minimum limit supervision of AI1 active.
1 = Maximum limit supervision of AI1 active.
1 = Minimum limit supervision of AI2 active.
1 = Maximum limit supervision of AI2 active.
Activation of analog input supervision.
Value of analog input AI1 in mA or V (depending on
whether the input is set to current or voltage by jumper
J1).
Value of analog input AI1.
Value of analog input AI1 after scaling. See parameters
112.19 AI1 scaled at AI1 min
max.
Scaled value of analog input AI1.
Selects the unit for readings and settings related to
analog input 1.
Milliamperes.
Volts.
Defines the filter time constant for analog input AI1.
%
Unfiltered signal
100
63
Filtered signal
T
-t
/T
O = I × (1 - e
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Note: The signal is also filtered due to the signal
interface hardware (approximately 0.25 ms time
constant). This cannot be changed by any parameter.
Filter time constant.
Defines the minimum value for analog input AI1. See the
drawing at parameter
Minimum value of AI1.
Defines the maximum value for analog input AI1. See the
drawing at parameter
Maximum value of AI1.
function.
and
112.20 AI1 scaled at AI1
t
112.19 AI1 scaled at AI1
112.19 AI1 scaled at AI1
Parameters 61
Def/FbEq16
0000b
1 = 1
-
1000 = 1 mA
or V
-
1 = 1
V
10
2
0.000 s
1000 = 1 s
0.000 V
min.
1000 = 1 V or
mA
20.000 V
min.
1000 = 1 V or
mA

Advertisement

Table of Contents
loading