ABB ACS880 Firmware Manual page 114

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

114 Parameters
No.
Name/Value
Option slot 3
150.02
FBA A comm loss
func
No action
Fault
Fault always
Warning
150.03
FBA A comm loss t
out
0.3 ... 6553.5 s
150.07
FBA A actual 1 type
Transparent
General
150.08
FBA A actual 2 type
150.10
FBA A act1
transparent source
Not selected
Other [bit]
150.11
FBA A act2
transparent source
Not selected
Other [bit]
150.12
FBA A debug mode
Disable
Fast
Description
Communication between supply unit and fieldbus
adapter A enabled. The adapter is in slot 3.
Selects how the supply unit reacts upon a fieldbus
communication break. The time delay is defined by
parameter
150.03 FBA A comm loss t
Communication break detection disabled.
Communication break detection active. Upon a
communication break, the diode supply unit trips on a
communication fault.
The supply unit trips on a communication fault even
though no control is expected from the fieldbus.
The supply unit generates a communication warning
even though no control is expected from the fieldbus.
Defines the time delay before the action defined by
parameter
150.02 FBA A comm loss func
count starts when the communication link fails to
update the message.
Time delay.
Selects the type and scaling of actual value 1
transmitted to the fieldbus network through fieldbus
adapter A.
No scaling is applied.
Generic reference without a specific unit.
Selects the type and scaling of actual value 2
transmitted to the fieldbus network through fieldbus
adapter A.
For the selections, see parameter
type.
When parameter
150.07 FBA A actual 1 type
Transparent, this parameter selects the source of actual
value 1 transmitted to the fieldbus network through
fieldbus adapter A.
No source selected.
Source selection (see
Terms and abbreviations
39).
When parameter
150.08 FBA A actual 2 type
Transparent, this parameter selects the source of actual
value 2 transmitted to the fieldbus network through
fieldbus adapter A.
No source selected.
Source selection (see
Terms and abbreviations
39).
Enables the display of raw (unmodified) data received
from and sent to fieldbus adapter A in parameters
150.13...150.18.
Note that the changes made take effect only after
reboot or setting the parameter
to Refresh.
This functionality should only be used for debugging.
Display of raw data from fieldbus adapter A disabled.
Debug mode is enabled. Cyclical data update is as fast
as possible which increases the CPU load on the supply
unit.
out.
is taken. Time
150.07 FBA A actual 1
is set to
on page
is set to
on page
151.27 FBA A par refresh
Def/FbEq16
3
No action
0
1
4
5
0.3 s
10 = 1 s
Transparent
1
2
Transparent
Not selected
-
-
Not selected
-
-
Disable
0
1