Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Fault
(hex)
5E07
PU communication
5E08
Power unit lost
5E09
PU communication
internal
5E0A
Measurement circuit
ADC
5E0B
PU board powerfail
5E0C
Measurement circuit
DFF
5E0D
PU communication
configuration
Cause
The way the control unit is
powered does not
correspond to parameter
setting.
Communication errors
detected between the
control unit and the power
unit.
Connection between the
control unit and the power
unit is lost.
Internal communication
error.
Measurement circuit fault.
Power unit power supply
failure.
Measurement circuit fault.
Version check cannot find a
matching power unit FPGA
logic, or number of
connected power modules
differs from specified.
Fault tracing 181
What to do
Check setting of
195.04 Control board
supply.
Check the connection between the
control unit and the power unit.
Check the auxiliary code (format XXXY
YYZZ). With parallel-connected
modules, "Y YY" specifies the affected
control unit channel (0: broadcast).
"ZZ" specifies the error source (1:
Transmitter side [link error], 2:
Transmitter side [no communication],
3: Receiver side [link error], 4: Receiver
side [no communication], 5:
Transmitter FIFO error [see "XXX"], 6:
Module [xINT board] not found, 7:
BAMU board not found). "XXX"
specifies the transmitter FIFO error
code (1: Internal error [invalid call
parameter], 2: Internal error
[configuration not supported],
3: Transmission buffer full).
Check the connection between the
control unit and the power unit.
Contact your local ABB representative.
Contact your local ABB representative,
quoting the auxiliary code.
Check the auxiliary code (format ZZZY
YYXX). "YY Y" specifies the affected
module (0...C). "XX" specifies the
affected power supply (1: Power
supply 1, 2: Power supply 2, 3: both
supplies).
Contact your local ABB representative,
quoting the auxiliary code.
If the number of connected power
modules is correct (parameter
Parallel connection rating
the FPGA logic of the power unit.
Cycle the power to the supply unit. If
the control unit is externally powered,
also reboot the control unit (using
parameter
196.08 Control board
or by cycling its power.
If the problem persists, contact your
local ABB representative.
195.31
id), update
boot)