ABB ACS880 Firmware Manual page 97

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
131.06
External event 3
type
Fault
Warning
Warning/Fault
131.07
External event 4
source
131.08
External event 4
type
Fault
Warning
Warning/Fault
131.09
External event 5
source
131.10
External event 5
type
Fault
Warning
Warning/Fault
131.11
Fault reset
selection
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
Description
Selects the type of external event 3.
The external event generates a fault.
The external event generates a warning.
If the diode supply unit is running, the external event
generates a fault. Otherwise, the event generates a
warning.
Defines the source of external event 4. See also
parameter
131.08 External event 4
For the selections, see parameter
source.
Selects the type of external event 4.
The external event generates a fault.
The external event generates a warning.
If the diode supply unit is running, the external event
generates a fault. Otherwise, the event generates a
warning.
Defines the source of external event 5. See also
parameter
131.10 External event 5
For the selections, see parameter
source.
Selects the type of external event 5.
The external event generates a fault.
The external event generates a warning.
If the diode supply unit is running, the external event
generates a fault. Otherwise, the event generates a
warning.
Selects the source of an external fault reset signal. The
signal resets the supply unit after a fault trip if the cause
of the fault no longer exists.
0 - > 1 = Reset
Note: A fault reset from the fieldbus interface is always
observed regardless of this parameter.
0.
1.
Digital input DI1 (as indicated by
status, bit 0).
Note: DI1 is reserved for temperature fault in the control
program. Do not select it for any other use.
Digital input DI2 (as indicated by
status, bit 1).
Digital input DI3 (as indicated by
status, bit 2).
Note: DI3 is reserved for main breaker/contactor fault in
the control program. Do not select it for any other use.
Digital input DI4 (as indicated by
status, bit 3).
Note: DI4 is reserved for auxiliary circuit breaker fault in
the control program. Do not select it for any other use.
Digital input DI5 (as indicated by
status, bit 4).
Parameters 97
type.
131.01 External event 1
type.
131.01 External event 1
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
Def/FbEq16
Fault
0
1
3
Inactive
(true)
Fault
0
1
3
Inactive
(true)
Fault
0
1
3
DI6
0
1
2
3
4
5
6