ABB ACS880 Firmware Manual page 47

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
106.11
Main status word
0000h...FFFFh
106.16
Drive status word 1
0000h...FFFFh
Description
Main status word of the diode supply unit.
Reflects the status of the supply unit irrespective of
control source, eg. a fieldbus system, control panel
(keypad), PC tool, standard I/O, application program or
sequence programming, and irrespective of actual
control profile which is used to control the supply unit.
This parameter is read-only.
The bit assignments are shown in the table below. For
detailed bit descriptions, see page 193.
Bit
Name
0
Ready to switch ON
1
Ready run
2
Ready ref
3
Tripped
4
-
5
-
6
-
7
Warning
8
Operating
9
Remote
10
Ready for load
11
User bit 0
12
User bit 1
13
User bit 2
14
Charging
15
User bit 3
Main status word.
Status word 1 of the supply unit.
This parameter is read-only.
Bit
Name
0
Enabled
1
Inhibited
2
Reserved
3
Reserved
4
Reserved
5
Started
6
Reserved
7
Reserved
8
Local control
9
Network control
10
Ext1 active
11
Ext2 active
12
Charging
13
MCB
14...15
Reserved
Status word 1.
Description
1 = Run enable and start enable
signals are present
1 = Start inhibited
1 = DSU has been started
1 = DSU is in local control
1 = DSU is in network control
1 = Control location Ext1 active
1 = Control location Ext2 active
1 = Charging relay is closed
1 = MCB relay is closed
Parameters 47
Def/FbEq16
-
1 = 1
-
1 = 1