134 Parameters
No.
Name/Value
[Drive/supply unit
type]
195.38
DOL fan start
delay
0...60 s
196

196 System

196.01
Language
Not selected
English
196.02
Pass code
0...99999999
196.03
Access levels
active
0000h...FFFFh
196.06
Parameter restore
Done
Restore defs
Description
Drive/supply unit type consisting of parallel-connected
modules.
Defines the start delay for a direct-on-line fan.
Start delay for a direct-on-line fan.
Language selection; pass code; parameter save and
restore; control unit reboot; user lock.
Selects the language of the parameter interface and
other displayed information.
No language selected.
English.
Pass codes can be entered into this parameter to
activate further access levels (see parameter
Access levels
active) or to configure the user lock.
Entering "358" toggles the parameter lock, which
prevents the changing of all other parameters through
the control panel or the Drive composer PC tool.
Entering the user pass code (by default, "10000000")
enables parameters 196.100...196.102, which can be
used to define a new user pass code and to select the
actions that are to be prevented.
Entering an invalid pass code will close the user lock if
open, ie. hide parameters 196.100...196.102. After
entering the code, check that the parameters are in fact
hidden.
Note: You must change the default user pass code to
maintain a high level of cybersecurity. Store the code in
a safe place – the protection cannot be disabled even by
ABB if the code is lost.
See also section
User lock
Pass code.
Shows which access levels have been activated by pass
codes entered into parameter
Bit
Name
0
End user
1
Service
2
Advanced programmer
3...10
Reserved.
11
OEM access level 1
12
OEM access level 2
13
OEM access level 3
14
Parameter lock
15
Reserved.
Active access levels.
Restores the original settings of the control program, ie.
parameter default values.
Note: This parameter cannot be changed while the
diode supply unit is running.
Restoring is completed.
All parameter values are restored to default values,
except fieldbus adapter and drive-to-drive link data.
196.03
(page 37).
196.02 Pass
code.
Def/FbEq16
-
7 s
1 = 1
Not selected
0
1033
0
1 = 1
0000b
-
Done