ABB ACS880 Firmware Manual page 91

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
In1P Start; In2 Stop The sources of the start and stop commands are
Keypad
Fieldbus A
DDCS controller
120.02
Ext1 start trigger
Edge
Level
120.03
Ext1 in1
Off
On
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
Description
selected by parameters
in2. The state transitions of the source bits are
interpreted as follows:
State of source 1
(120.03)
0 - > 1
Any
Any
The start and stop commands are taken from the
control panel (or PC connected to the control panel).
The start and stop commands are taken from fieldbus
adapter A.
The start and stop commands are taken from an
external (DDCS) controller.
Defines whether the start signal for external control
location EXT1 is edge-triggered or level-triggered.
Note: In case the settings of parameters
120.02
are in conflict, the setting of parameter
takes preference.
The start signal is edge-triggered.
The start signal is level-triggered.
Selects source 1 for external control location EXT1. See
parameter
120.01 Ext1
0.
1.
Digital input DI1 (as indicated by
status, bit 0).
Note: DI1 is reserved for temperature fault in the control
program. Do not select it for any other use.
Digital input DI2 (as indicated by
status, bit 1).
Digital input DI3 (as indicated by
status, bit 2).
Note: DI3 is reserved for main breaker/contactor fault in
the control program. Do not select it for any other use.
Digital input DI4 (as indicated by
status, bit 3).
Note: DI4 is reserved for auxiliary circuit breaker fault in
the control program. Do not select it for any other use.
Digital input DI5 (as indicated by
status, bit 4).
Digital input DI6 (as indicated by
status
bit 5).
Digital input/output DIO1 (as indicated by
delayed
status, bit 0).
Digital input /output DIO2 (as indicated by
delayed
status, bit 1).
Source selection (see
Terms and abbreviations
39).
120.03 Ext1 in1
and
120.04 Ext1
State of source 2
Command
(120.04)
1
1 - > 0
0
120.01
commands.
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
110.02 DI delayed
111.02 DIO
111.02 DIO
Parameters 91
Def/FbEq16
4
Start
Stop
Stop
11
12
16
Edge
and
120.01
0
1
DI2
0
1
2
3
4
5
6
7
10
11
on page
-