ABB ACS880 Firmware Manual page 122

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

122 Parameters
No.
Name/Value
160.51
DDCS controller
comm port
No connect
Slot 1A
Slot 2A
Slot 3A
Slot 1B
Slot 2B
Slot 3B
XD2D
RDCO CH 0
160.52
DDCS controller
node address
1...254
160.55
DDCS controller
HW connection
Ring
Star
160.56
DDCS controller
baud rate
1 mbps
2 mbps
4 mbps
8 mbps
160.57
DDCS controller
link control
1...15
160.58
DDCS controller
comm loss time
0 ... 60000 ms
160.59
DDCS controller
comm loss action
No action
Fault
Warning
Description
Selects the DDCS channel used for connecting an
external controller (such as an AC 800M or ACS880
inverter).
None (communication disabled).
Channel A on FDCO module in slot 1.
Channel A on FDCO module in slot 2.
Channel A on FDCO module in slot 3.
Channel B on FDCO module in slot 1.
Channel B on FDCO module in slot 2.
Channel B on FDCO module in slot 3.
Connector XD2D.
Channel 0 on RDCO module (with UCU control unit only). 11
Selects the node address for communication with the
external controller. No two nodes on-line may have the
same address.
Node address.
Selects the topology of the fiber optic link.
The devices are connected in a ring topology.
Forwarding of messages is enabled.
The devices are connected in a star topology (for
example, through a branching unit). Forwarding of
messages is disabled.
Defines the communication speed on the fiber optic
link. This should be set to the same value on all devices
on the link.
1 Mbps.
2 Mbps.
4 Mbps.
8 Mbps.
Defines the light intensity of the transmission LED of
RDCO module channel CH0. (This parameter is effective
only when parameter
160.51 DDCS controller comm port
is set to
RDCO CH
0. FDCO modules have a hardware
transmitter current selector.)
In general, use higher values with longer fiber optic
cables. The maximum setting is applicable to the
maximum length of the fiber optic link.
Light intensity.
Sets a time-out for communication with the external
controller. If a communication break lasts longer than
the time-out, the action specified by parameter
DDCS controller comm loss action
Time-out for communication with external controller.
Selects how the supply unit reacts to a communication
break between it and the external controller.
No action taken.
Supply unit trips on
7E11 DDCS controller comm
Supply unit generates an
loss
warning. This occurs even though no control is
expected from the external controller.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
is taken.
AE6D DDCS controller comm
Def/FbEq16
No connect
0
1
2
3
4
5
6
7
1
1 = 1
Star
0
1
4 mbps
0
1
2
3
10
1 = 1
100 ms
160.59
1 = 1
Fault
0
loss.
1
5