184 Fault tracing
Code
Fault
(hex)
6E15
Text data overflow
6E16
Text 32-bit table
overflow
6E17
Text 64-bit table
overflow
6E18
Text file overflow
6E1A
Rating ID fault
6E1B
Backup/Restore
Timeout
6E1C
Emergency stop fault Diode supply unit has
6E1D
Internal SW error
6E1F
Licensing fault
6E20
Fault reset
6E27
Adaptive program
000A
000C
000E
0011
0012
001C
001D
001E
Cause
Internal fault.
Internal fault.
Internal fault.
Internal fault.
Rating ID load error.
A control panel or PC tool
fails to communicate with
the drive during backup or
restoring operation.
received an emergency stop
command.
Internal error.
Running the control program
is prevented either because a
restrictive license exists, or
because a required license is
missing.
Fault reset has been
requested and done.
Error running the adaptive
program.
Program corrupted or block
non-existent
Required block input missing Check the inputs of the block.
Program corrupted or block
non-existent
Program too large.
Program is empty.
A non-existing parameter or
block is used in the program.
Parameter type invalid for
selected pin.
Output to parameter failed
because the parameter was
write-protected.
What to do
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Contact your local ABB representative.
Check the control panel or PC tool
communication, and if it is still in
backup/restore state.
Check that it is safe to continue
operation.
Return the emergency stop
pushbutton to normal position.
Restart the supply unit.
Contact your local ABB representative.
Quote the auxiliary code (check the
event details in the event log).
Record the auxiliary codes of all active
licensing faults and contact your
product vendor for further
instructions.
Informative fault.
Check the auxiliary code (format
XXXX YYYY). "XXXX" specifies the
number of the function block (0000 =
generic error). "YYYY" indicates the
problem (see actions for each code
below).
Restore the template program or
download the program to the supply
unit.
Restore the template program or
download the program to the supply
unit.
Remove blocks until the error stops.
Correct the program and download it
to the supply unit.
Edit the program to correct the
parameter reference, or to use an
existing block.
Edit the program to correct the
parameter reference.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.