ABB ACS880 Firmware Manual page 101

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
Other [bit]
131.34
Cabinet
temperature
supervision
Always
When modulating
131.35
Main fan fault
function
Fault
Warning
No action
131.38
Fuse trip fault
source
Active (false)
Inactive (true)
DIIL
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other
131.39
Brake chopper
fault source
Description
Source selection (see
Terms and abbreviations
39).
Selects whether there is a delay in monitoring the
parameter
131.33 Cabinet temperature fault
this parameter is set to
monitoring is started after the modulation has started.
Otherwise there is no delay for the monitoring.
There is no delay for the monitoring.
Cabinet temperature monitoring is started after the
modulation has started.
Air-cooled units only: Selects how the supply unit reacts
when a main cooling fan fault is detected.
The supply unit trips on fault
The supply unit generates an
No action taken.
Activates/inactivates the monitoring for the fuse trip,
and defines the source for the monitored signal. If the
monitoring detects a fuse trip, the supply unit trips to
fault
5E1A Fuse
trip.
Status of the monitored signal and implication:
1 = No fault
0 = Fault.
Monitoring function is active.
Monitoring function is inactive.
Monitoring function is active and it reads the status
indication through DIIL
Monitoring function is active and it reads the status
indication through DI1
Monitoring function is active and it reads the status
indication through DI2
Monitoring function is active and it reads the status
indication through DI3
Monitoring function is active and it reads the status
indication through DI4
Monitoring function is active and it reads the status
indication through DI5
Monitoring function is active and it reads the status
indication through DI6
Monitoring function is active and it reads the status
indication through DIO1
0).
Monitoring function is active and it reads the status
indication through DIO2
1).
Source selection (see
Terms and abbreviations
39).
Activates/inactivates the monitoring for the brake
chopper fault, and defines the source for the monitored
signal. If the monitoring detects a brake chopper fault,
the supply unit trips to fault
Monitoring is active only when the supply unit is
running.
Status of the monitored signal and implication:
1 = No fault
0 = Fault.
source. If
When
modulating, the
5E00
Fan.
AE73 Fan
warning.
(110.02 DI delayed
status, bit 15).
(110.02 DI delayed
status, bit 0).
(110.02 DI delayed
status, bit 1).
(110.02 DI delayed
status, bit 2).
(110.02 DI delayed
status, bit 3).
(110.02 DI delayed
status, bit 4).
(110.02 DI delayed
status, bit 5).
(111.02 DIO delayed
status, bit
(111.02 DIO delayed
status, bit
5EA1 SoC
overtemperature.
Parameters 101
Def/FbEq16
on page
-
When
modulating
0
1
Warning
0
1
2
Inactive
(true)
0
1
2
3
4
5
6
7
8
11
12
on page
-
Inactive
(true)