No.
Name/Value
114.16
DIO2 output
source
114.17
DI2 ON delay
0.00 ... 3000.00 s
114.17
DIO2 ON delay
*DIO status
**Delayed DIO
status
t
=
114.17 DIO2 ON delay
On
t
=
114.18 DIO2 OFF delay
Off
*Electrical status of DIO (in input mode) or status of selected source (in output mode).
Indicated by
**Indicated by
0.0 ... 3000.0 s
114.18
DI2 OFF delay
0.00 ... 3000.00 s
114.18
DIO2 OFF delay
0.0 ... 3000.0 s
114.19
DIO3 configuration
Input
Output
114.19
AI supervision
function
No action
Fault
Warning
Description
(Visible when
114.01 Module 1 type
Selects a signal to be connected to digital input/output
DIO2 when parameter
Output.
For the available selections, see parameter
output
source.
(Visible when
114.01 Module 1 type
Defines the activation delay for digital input DI2. See
parameter
114.12 DI1 ON
Activation delay for DI2.
(Visible when
114.01 Module 1 type
Defines the activation delay for digital input/output
DIO2.
t
t
On
Off
114.05 DIO
status.
114.06 DIO delayed
status.
Activation delay for DIO2.
(Visible when
114.01 Module 1 type
Defines the deactivation delay for digital input DI2. See
parameter
114.12 DI1 ON
Deactivation delay for DI2.
(Visible when
114.01 Module 1 type
Defines the deactivation delay for digital input/output
DIO2. See parameter
Deactivation delay for DIO2.
(Visible when
114.01 Module 1 type
Selects whether DIO3 of the extension module is used as
a digital input or output.
DIO3 is used as a digital input.
DIO3 is used as a digital output.
(Visible when
114.01 Module 1 type
Selects how the supply unit reacts when an analog input
signal moves out of the minimum and/or maximum
limits specified for the input.
The inputs and the limits to be observed are selected by
parameter
114.20 AI supervision
No action taken.
Supply unit trips on
Supply unit generates an
=
FIO-01
114.14 DIO2 configuration
= FDIO-01)
delay.
=
FIO-01
t
t
On
Off
= FDIO-01)
delay.
=
FIO-01
114.17 DIO2 ON
delay.
= FIO-01)
=
FIO-11
selection.
8E06 AI
supervision.
AE67 AI supervision
Parameters 69
Def/FbEq16
or FIO-11)
Not
energized
is set to
114.11 DIO1
0.00 s
10 = 1 s
or FIO-11)
0.0 s
1
0
1
0
Time
10 = 1 s
0.00 s
10 = 1 s
or FIO-11)
0.0 s
10 = 1 s
Input
0
1
or FAIO-01)
No action
0
1
warning.
2