Table 58: Parts Required for Connecting an EX Series Switch to Earth Ground
Switch
Earthing
Terminal
Location
EX8216
Two earthing
terminals:
Left side
of the
chassis
Rear
panel of
the
chassis
NOTE: You
must use
only one of
the two
protective
earthing
terminals.
EX9204,
Rear panel of
EX9208,
the chassis
and
EX9214
Grounding
Grounding Lug
Cable
Specifications
Requirements
2 AWG
Panduit LCD2-14A-
(33.6 mm²),
Q or equivalent
minimum 90° C
—provided
wire, or as
permitted by
the local code
One 6 AWG
Thomas& Betts
(13.3 mm²),
LCN6-14 or
minimum 90° C
equivalent—
wire, or one
provided
that complies
with the local
code
(Continued)
Screws and
Additional
Washers
Information
Two ¼ -20 x
0.5 in.
screws with
#¼" split-
washer
—provided
Two #¼" flat
washers—
provided
See
Grounding
Two ¼ -20
Cable and Lug
x 0.5 in.
Specifications for
screws with
EX9200
#¼" split-
washer—
provided
Two #¼" flat
washers—
provided
170