Juniper EX9214 Hardware Manual page 284

Hide thumbs Also See for EX9214:
Table of Contents

Advertisement

Ensure that you have the following parts and tools available:
• An ESD wrist strap
• 2.5 mm flat-blade screwdriver
To connect the alarm relay wires between a switch and an alarm-reporting device (see
273):
1. Prepare the required length of replacement wire with gauge between 28 AWG (0.08 mm
2
14 AWG (2.08 mm
).
2. Insert the replacement wires into the slots in the front of the block. Use the screwdriver to tighten
the screws and secure the wire.
3. Wrap and fasten one end of the ESD wrist strap around your bare wrist, and connect the other end
of the strap to the ESD point on the switch.
4. Plug the terminal block into the relay contact, and use the screwdriver to tighten the screws on the
face of the block.
5. Attach the other end of the wires to the external device.
Figure 89: Alarm Relay Contacts
SEE ALSO
Connecting the EX9200 Switch to an External Alarm-Reporting Device
Craft Interface in an EX9200 Switch | 29
Figure 89 on page
2
) and
273

Advertisement

Table of Contents
loading

Table of Contents