Juniper EX9214 Hardware Manual page 178

Hide thumbs Also See for EX9214:
Table of Contents

Advertisement

Table 58: Parts Required for Connecting an EX Series Switch to Earth Ground
Switch
Earthing
Terminal
Location
EX3200
Rear panel of
and
the chassis
EX3300
EX3400
Rear panel of
the chassis
EX4200
Left side of
the chassis
Grounding
Grounding Lug
Cable
Specifications
Requirements
14 AWG
Panduit
(2 mm²),
LCC10-14BWL or
minimum 90° C
equivalent—
wire, or as
not provided
permitted by
the local code
14-10 AWG
Panduit
STR (2.5-6
LCD10-10A-L or
mm²), minimum
equivalent—
90° C wire, or
not provided
as permitted by
the local code
14 AWG
Panduit
(2 mm²),
LCC10-14BWL or
minimum 90° C
equivalent—
wire, or as
not provided
permitted by
the local code
(Continued)
Screws and
Additional
Washers
Information
For EX3200
Two
Switches, see
10-32 x .25 i
"Special Instructions
n. screws
to Follow Before
with #10
Connecting Earth
split-lock
Ground to an EX
washer—
Series Switch" on
not provided
page
171.
Two #10 flat
washers—
not provided
Two
10-32 x .25 i
n. screws
with #10
split-lock
washer—
not provided
Two #10 flat
washers—
not provided
See
"Special
Two 10-32
Instructions to
x .25 in.
Follow Before
screws with
Connecting Earth
#10 split-
Ground to an EX
lock washer
Series Switch" on
page
171.
not provided
Two #10 flat
washers—
not provided
167

Advertisement

Table of Contents
loading

Table of Contents