7.2 USER-DEFINED PERIOD OUTPUT

Defined Period output is composed by 2 parts, period output S1 and condition output S2.
While S1 and S2 are TRUE synchronously, OUTPUT;
While S1 or S2 is FALSE, NOT OUTPUT.
Period output S1 can set generator's one or more period output freely, can set the delayed time and
output time after enter into period.
Condition output S2 can set as any conditions in output ports.
NOTE: when delay time and output time both are 0 in period output S1, it is TRUE in this period.
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 active, after enter ―starts time‖ and delay 2s, this defined period output is outputting, after
3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
Action when input port 1 is active
Action when input port 2 is active
Action when input port 3 is active
Action when input port 4 is active
Action when input port 5 is active
Action when input port 1 is active