No.
Item
92
Reserved
93
Aux Input 1 Active
94
Aux Input 2 Active
95
Aux Input 3 Active
96
Aux Input 4 Active
97
Aux Input 5 Active
98
Aux Input 6 Active
99
Reserved
7.2 USER-DEFINED PERIOD OUTPUT
Defined Period output is composed by 2 parts, period output S1 and condition output S2.
While S1 and S2 are TRUE synchronously, OUTPUT;
While S1 or S2 is FALSE, NOT OUTPUT.
Period output S1 can set generator's one or more period output freely, can set the delayed time and
output time after enter into period.
Condition output S2 can set as any conditions in output ports.
NOTE: when delay time and output time both are 0 in period output S1, it is TRUE in this period.
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 active, after enter ―starts time‖ and delay 2s, this defined period output is outputting, after
3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
Action when input port 1 is active
Action when input port 2 is active
Action when input port 3 is active
Action when input port 4 is active
Action when input port 5 is active
Action when input port 1 is active
Version 1.0
Description
2016-12-07
Page 31 of 54