Defined Contents Of Programmable Output Ports 1-5 - Smartgen HGM400N Series User Manual

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

7.2

DEFINED CONTENTS OF PROGRAMMABLE OUTPUT PORTS 1-5

Table 8 Defined Contents of Programmable Output Ports 1-5
No.
Items
0
Not Used
1
Common Alarm
2
Energized to Stop
3
Idle Control
4
Preheat Control
5
Close Generator
6
Mains Closed
7
Open ATS
8
Raise Speed
9
Drop Speed
10
Normal Run
11
Fuel Pump Control
12
High Speed Control
13
In Auto Mode
14
Fuel Relay Output
15
Generator Excite
16
Colling Fan Output
17
Louver Control
18
Shutdown Alarm
19
Audible Alarm
20
Coolant Heating Control
21~31 Reserved
HGM400N Series Genset Controller User Manual
Output port is deactivated when "Not Used" is selected.
Include all shutdown alarms and warning alarms. When there is
warning alarm only, it is not self-lock; when a shutdown alarm
occurs, it is self-lock until the alarm is reset.
Suitable for genset with electromagnet and will active after "ETS
delay". It is deactivated when the "ETS delay" expires.
Used for genset which has idles. Close before starting and open in
warming up delay; Close during stop idle delay and open when stop
is completed.
Close before starting and open before power up.
When close time is 0, it's continuous output.
HGM410N without.
When close time is 0, it's disabled.
Close when the generator enters into Warming Up delay (close time:
warming up delay) while open when Aux.
Close when the generator enters into Stop Idle delay/Energized to
Stop delay (close time: stop idle delay) while open when Aux.
Action when genset is normally running and disconnect when speed
is lower than crank disconnect speed.
Close when fuel level is lower than the "Fuel Pump On" value or
when low fuel level warning input is active; Open when fuel level is
higher than the "Fuel Pump Off" and low fuel level warning input is
deactivated.
Close when the generator enters into Warming Up delay while open
after cooling delay.
The controller is in automatic mode.
Close when the generator enters into Warming Up delay while open
after cooling delay.
Output in start period. If there is no generator frequency during
safety running, output for 2 seconds.
Control air blower to start/stop according to temperature.
Action when genset starting and disconnect when genset stopped
completely.
Alarm when genset shutdown.
When shutdown alarm and warn alarm occur, audible alarm is set as
300s. In audible alarm output duration, when panel any key or "alarm
mute" input is active, it can remove the alarm.
It is controlled by cooler of temperature sensor's limited threshold.
Description
Page 26 of 38