8.2.2

CUSTOM PERIOD OUTPUT

Defined period output is composed by 2 parts: period output S1 and condition output S2.
S1 and S2 both are true, then it outputs; S1 or S2 is false, it doesn't output;
Period output S1 can be configured randomly to one, or several period outputs; Delay time and
output time after entering period can be set;
Condition output S2 can be any contents of output settings.
NOTE: When period output S1 delay time and output time are both 0, configurations of period output S1 are both true.
Output period: Start
Delay output time: 2s
Output time: 3s
Condition output contents: Input 1 is active;
Condition output active/inactive close; close when active (disconnect when inactive)
When input port 1 is active, and it enters start time and delays for 2s, custom period output starts
to output, after outputting for 3s, it stops outputting;
When input port 1 is inactive, custom output doesn't output.
8.2.3

DEFINED COMBINATION OUTPUT

Defined combination output is composed by 3 parts: OR condition output S1, OR condition output
S2, AND condition output S3.
S1 or S2 is true, and S3 is true, then combination output works.
S1 and S2 both are false, or S3 is false, then combination output doesn't work.
NOTE: S1, S2 and S3 can be any contents except itself defined combination output of the output settings.
NOTE: S1, S2 and S3 cannot include or recursively include itself.
Contents of OR condition output S1: input port 1 is active;
Close when OR condition output S1 is active/inactive: close when active (disconnect when
inactive);
Contents of OR condition output S2, input port 2 is active;
Close when OR condition output S2 is active/inactive: close when active (disconnect when
inactive);
Contents of AND condition output S3: input port 3 is active;
Close when AND condition output S3 is active/inactive: close when active (disconnect when
inactive);
When input port 1 is active or input port 2 is active, if input port 3 is active, defined combination
output is working; if input port 3 is inactive, defined combination output is not working;
When input port 1 is inactive and port 2 is inactive, no matter port 3 is active or not, defined
combination output is not working.
HEM4300 Engine Controller User Manual