User Menu And Parameters Setting - Smartgen HGM9600 Series User Manual

Genset controller
Table of Contents

Advertisement

NOTE: Power factor shows as following,
Power factor
Conditions
COS>0L
P>0,Q>0
COS>0C
P>0,Q<0
COS<0L
P<0,Q>0
COS<0C
P<0,Q<0
NOTE:
1.
Input active power, generator or mains supplies electricity to load.
2.
Output active power, load supplies electricity to generator or mains.
3.
Input reactive power, generator or mains sends reactive power to load.
4.
Output reactive power, load sends reactive power to generator or mains.
★Alarm:
NOTE: For ECU alarms and shutdown alarms, if the alarm information is displayed, check engine according to it,
otherwise, please check the manual of engine according to SPN alarm code.
Event log
Records all start/stop events (shutdown alarm, trip and shutdown alarm, manual /auto start or stop) and
the real time when alarm occurs.
Others, including,
Time and date, count down time for maintenance (if it is enable), input/output ports status, NET status and
SD status.
About, including,
Issue time of software and hardware version, product PD number.
5.3.2

USER MENU AND PARAMETERS SETTING

Press and hold
★Parameter
After entering the correct password (factory default password is 00318) you can enter parameter
HGM9600 Series Genset Controller User Manual
Table 7 Power Factor Description
Active power
Input
Input
Output
Output
for more than 3 seconds to enter user menu;
Remark:
P stands for active power
Q stands for reactive power
Reactive power
Input
Load is inductive resistance.
Output
Load is capacitance resistance.
Load
Input
excitation generator
Load
Output
excitation generator.
Remark
equals
to
one
under
equals
to
one
Page 16 of 73
over

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9610Hgm9620

Table of Contents