5.3 MAIN MENU
Press and hold
Content
NOTE: Input password to enter parameter settings, default password "01234"; operator can change the password to
prevent others changing controller configurations. After change please remember clearly; If it is forgotten, please
contact company service personnel.
6 PARAMETER SETTING
6.1 SETTING INSTRUCTIONS
Press and hold
press
OFF key to confirm and enter the password confirmation interface. Input the correct
password to enter the parameter main interface, if the password is incorrect, exit and return to the main
screen, the factory default password is:
6.2 PARAMETER CONFIGURATION TABLE
No.
Parameter
1
Sensor Curve Type
2
Open Action
Custom
Curve
3
Content
4
Unit
5
Cut-out Pressure
6
FPC1700 Jockey Pump Controller User Manual
OFF key in main display screen to enter the main menu.
Table 8 Main Menu Display
Press
to select the different parameter lines, and then press
to enter the corresponding display screen.
OFF key in home page to enter the menu, select "1. Parameter Setting", then
01234.
Table 9 Parameter Setting Description
Default
Range
1
(0-3)
0
(0-1)
0
(0-3)
1000 kPa
(0-9000) kPa
3
(0-3600)s
Description
Description
0: Not used
1: Custom resistance curve
2: Custom 4-20 mA
3: Custom voltage curve
0: Warn
1: No Action
0: kPa
1: bar
2: psi
3: MPa
Shutdown when pipe pressure is greater
than the cut-out pressure threshold value.
Page 10 of 17