UPS Maintenance
a.
Remove one top screw and two bottom screws securing the FI-UPM front panel (refer to the Eaton
Power Xpert
panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
b.
Pull the foam filter over the screw heads on the cabinet mounted studs and remove the filter from the
cabinet.
Verify washed filter is thoroughly dry before reinstalling.
Vérifier que les filtres sont bien secs avant de les réinstaller.
c.
Push the washed or new foam filter over the screw heads on the cabinet mounted studs until seated
against the cabinet.
d.
Reinstall the FI-UPM front panel removed in Step a and secure with the retained hardware.
4.
Record maintenance results and any corrective actions in a suitable log.
FI-UPM Air Filter

Figure 9-2. FI-UPM Air Filter Location

®
9-4
Eaton
Power Xpert
®
9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503)). Lift the
®