5.4

Operator Programming Errors

An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an
individual parameter setting is inappropriate.

oPE Codes, Causes, and Possible Solutions

Table 5.4 oPE Codes, Causes, and Possible Solutions
LED Operator Display
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
5.4 Operator Programming Errors
Drive Capacity Setting Fault
oPE01
Drive capacity and then value set to o2-04 do not match.
Parameter Range Setting Error
oPE02
Use U1-18 to find which parameters were set outside the
setting range.
Multi-Function Input Selection Error
oPE03
A contradictory setting is assigned to multi-function
contact inputs H1-01 through to H1-07.
oPE04
Initialization required.
Run Command Selection Error
oPE05
The Run command selection parameter b1-02 is set to 3
but no option board is installed.
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function
oPE07
analog inputs H3-02 through to H3-10 and PID functions
conflict.
Parameter Selection Error
oPE08
A function has been set that cannot be used in the motor
control method selected.
PID Control Selection Fault
oPE09
PID control function selection is incorrect.
Requires that PID control is enabled (b5-01 = 1 to 4).
V/f Data Setting Error
The following setting errors have occurred where:
E1-04 is greater than or equal to E1-06 is greater than or
oPE10
equal to E1-07 is greater than or equal to E1-09.
Or the following setting errors have occurred:
E3-04 is greater than or equal to E3-06 is greater than or
equal to E3-07 is greater than or equal to E3-09.
Carrier Frequency Setting Error
oPE11
Correct the setting for the carrier frequency.