4.5 Basic Drive Setup Adjustments
5.
Press the
STOP
until the motor comes to a complete stop.
Run the Drive using Digital Input Terminals: b1-02 = 1
This setting uses the digital input terminals to enter the run command. The factory setting is
a 2-wire sequence.
Using a 2-Wire Sequence
Digital Input Terminals
S1
S2
Figure 4.8
Using a 3-Wire Sequence
When H1-05 (Multi-Function Digital Input Terminal S5 Function Selection) = 0, the
functions of terminals S1 and S2 are set to 3-wire sequence, and the multi-function input
terminal becomes forward/reverse run command terminal.
Figure 4.9
Figure 4.9 Example Wiring Diagram for 3-Wire Sequence Using Terminal S5
Note: When terminal S5 is open, the motor rotates forward. When closed, the motor rotates in reverse.
70
Step
key to stop the motor. The RUN light will flash
Forward Run
Reverse Run
Figure 4.8 Example Wiring Diagram for 2-Wire Sequence
Stop Switch
Run Switch
(N.C.)
(N.O.)
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
ON
Forward Run
Reverse Run
Drive
S1
S2
SC
Digital Input Common
Drive
S1
Run Command
(runs when open)
S2
Stop Command
(stops when closed)
S5
FWD/REV Command
(multi-function input)*
SC
Digital Input Common
Display/Result
flashing
OFF
Stop
Stop
off