7.1 Parameter Table
H2-
Function
Setting
4
Frequency (FOUT) Detection 1
5
Frequency (FOUT) Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock
9
Option Reference
A
Local/Remote
B
Torque Detection 1 (N.O.)
C
Loss of Reference
D
Braking Resistor Fault
E
Fault
F
Not used
10
Alarm
11
Reset Command Active
12
Timer Output
13
Fref/Fout Agree 2
14
Fref/Fset Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
Reverse Direction
1B
Baseblock 2
128
H2 Multi-Function Digital Output Settings
Closed: Output frequency is less than or equal to the value in
L4-01 with hysteresis determined by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01,
with hysteresis determined by L4-02.
Closed: Drive Ready. The drive is powered up, not in a fault state, and
in the Drive mode.
Closed: DC bus voltage is below the UV trip level set in L2-05.
Closed: This is no output voltage
Closed: Digital operator supplies the frequency reference.
Open: Reference 1 or 2 are active
Closed: Digital operator supplies the run command.
Closed: Output current/torque exceeds the torque value set in parameter
L6-02 for longer than the time set in parameter L6-03.
Closed: Loss of the analog frequency reference detected. Enabled when
L4-05 = 1.
Closed: Braking resistor or transistor is overheated or faulted out.
Closed: Fault occurred (other than CPF00 and CPF01).
Set this value when the terminal is not used, or when using the terminal
in the pass-through mode.
Closed: An alarm is triggered.
Closed: Reset command to the drive is active.
Timer output, controlled by b4-01 and b4-02. Used in conjunction with
the digital input (H1-
Closed: When drive output frequency equals the frequency reference +/
- L4-04.
Closed: When the drive output frequency is equal to the value in L4-03
(plus or minus L4-04).
Closed: When the drive output frequency is less than or equal to the
value in L4-03 with the hysteresis determined by L4-04.
Closed: When the output frequency is greater than or equal to the value
in L4-03 with the hysteresis determined by L4-04.
Open: When the output current/torque exceeds the value set in
parameter L6-02 for more time than is set in parameter L6-03.
Closed: When the output current/torque exceeds the value set in
parameter L6-05 for more time than is set in parameter L6-06.
Open: Output current/torque exceeds the value set in parameter L6-05
for more time than is set in parameter L6-06.
Closed: Drive is running in the reverse direction.
Open: Drive is in base block condition. Output is disabled.
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
Description
= 18 "timer function").