3.4 Main Frequency Reference
Figure 3.12
Setting Value
V (left position)
I (right position)
No.
Parameter Name
Frequency ref. (current)
H3-09
terminal A2 signal level selection
48
Figure 3.12 DIP Switch S1
Table 3.13 DIP Switch S1 Settings
Current input (4 to 20 mA or 0 to 20 mA): factory setting
Table 3.14 Parameter H3-09 Details
Selects the signal level for terminal A2.
0: 0 to +10 V, unipolar input (negative frequency
reference values are zeroed)
1: 0 to +10 V, bipolar input (negative frequency
reference changes the direction)
2: 4 to 20 mA
3: 0 to 20 mA
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
DIP Switch S1
V
I
Description
Voltage input (0 to 10 V)
Description
Setting
Default
Range
Setting
0 to 3
2