Installing Fuses on the Input Side
Install recommended UL-approved fuses at the main power input of the drive. Select fuses
according to
Table
8.1.
Drive Model CIMR-V
BA0001
BA0002
BA0003
BA0006
BA0010
BA0012
2A0001
2A0002
2A0004
2A0006
2A0010
2A0012
2A0020
2A0030
2A0040
2A0056
2A0069
4A0001
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
Table 8.1 Recommended Input Fuse Selection
Time Delay/
Class RK5 Fuses
600 Vac, 200 kAIR
200 V Class Single-Phase Drives
TRS5R
TRS10R
TRS20R
TRS35R
TRS50R
TRS60R
200 V Class Three-Phase Drives
TRS5R
TRS5R
TRS10R
TRS15R
TRS25R
TRS35R
TRS60R
Not Available
400 V Class Three-Phase Drives
TRS2.5R
TRS5R
TRS10R
TRS20R
TRS20R
TRS20R
TRS30R
8.1 European Standards
Fuse Ampere Rating
5
10
20
35
50
60
5
5
10
15
25
35
60
70
100
150
200
2.5
5
10
20
20
20
30
Non-Time Delay/
Class T Fuses
600 Vac, 200 kAIR
Contact Yaskawa
Contact Yaskawa
A6T70
A6T100
A6T150
A6T200
Contact Yaskawa