YASKAWA V1000 Quick Start Manual page 119

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

No.
Name
Torque Compensation Primary
C4-06
Delay Time 2
Use C5 parameters to configure the Automatic Speed Regulator (ASR).
C5 parameters are available only when using V/f with Simple PG (H6-01 = 3).
C5-01 ASR Proportional Gain 1
C5-02 ASR Integral Time 1
C5-03 ASR Proportional Gain 2
C5-04 ASR Integral Time 2
C5-05 ASR Limit
Use C6 parameters to configure the carrier frequency drive settings.
C6-01 Normal / Heavy Duty Selection
C6-02 Carrier Frequency Selection
C6-03 Carrier Frequency Upper Limit
C6-04 Carrier Frequency Lower Limit
C6-05 Carrier Frequency Proportional Gain Refer to V1000 Technical Manual for details.
d1-01 Frequency Reference 1
d1-02 Frequency Reference 2
d1-03 Frequency Reference 3
d1-04 Frequency Reference 4
d1-05 Frequency Reference 5
d1-06 Frequency Reference 6
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
Refer to V1000 Technical Manual for details.
C5: Speed Control (ASR)
Refer to V1000 Technical Manual for details.
Refer to V1000 Technical Manual for details.
Refer to V1000 Technical Manual for details.
Refer to V1000 Technical Manual for details.
Refer to V1000 Technical Manual for details.
C6: Carrier Frequency
Refer to V1000 Technical Manual for details.
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
6: 15.0 kHz
7: Swing PWM1 (Audible sound 1)
8: Swing PWM2 (Audible sound 2)
9: Swing PWM3 (Audible sound 3)
A: Swing PWM4 (Audible sound 4)
B to E: No setting possible
F: User defined (determined by C6-03 through C6-05)
Refer to V1000 Technical Manual for details.
d1: Frequency Reference
Use d1 parameters to configure the drive frequency reference.
Frequency reference
Frequency reference when digital input "Multi-Step Speed Reference
1" (H1-
Frequency reference when digital input "Multi-Step Speed Reference
2" (H1-
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 2" (H1-
Frequency reference when digital input "Multi-Step Speed Reference
3" (H1-
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 3 " (H1-
7.1 Parameter Table
Description
= 3) is on.
= 4) is on.
= 3 and 4) are on.
= 5) is on.
= 3 and 5) are on.
7
119

Advertisement

Table of Contents
loading