7.1 Parameter Table
No.
H6-02
Pulse Train Input Scaling
H6-03
Pulse Train Input Gain
H6-04
Pulse Train Input Bias
H6-05
Pulse Train Input Filter Time
Pulse Train Monitor Terminal MP
H6-06
Selection
H6-07
Pulse Train Monitor Scaling
Motor Overload Protection
L1-01
Selection
L1-02
Motor Overload Protection Time
Motor Overheat Alarm Operation
L1-03
Selection (PTC input)
Motor Overheat Fault Operation
L1-04
Selection (PTC input)
Motor Temperature Input Filter
L1-05
Time (PTC input)
Continuous Electrothermal
L1-13
Operation Selection
Use L2 parameters to configure drive functions for momentary power loss conditions.
Momentary Power Loss Operation
L2-01
Selection
Momentary Power Loss Ride-Thru
L2-02
Time
Momentary Power Loss Minimum
L2-03
Baseblock Time
Momentary Power Loss Voltage
L2-04
Recovery Ramp Time
132
Name
Sets the number of pulses (Hz) that is equal to 100% of the value
selected in H6-01.
Sets the level of the value selected in H6-01 when a frequency with the
value set in H6-02 is input.
Sets the level of the value selected in H6-01 when 0 Hz is input.
Sets the pulse train input filter time constant.
Select the pulse train monitor output function (value of the
of U -
Sets the pulse output frequency in Hz when the monitor value is 100%.
L1: Motor Protection Functions
Use L1 parameters to configure motor protective functions.
0: Disabled
1: Standard Fan Cooled (< 10:1 motor)
2: Standard Blower Cooled (≥ 10:1 motor)
3: Vector Motor (100:1 motor)
4: PM motor with variable torque
NOTICE: The thermal protection is reset when the power is cycled. In
applications where the power is frequently cycled, the drive may not be
able to provide protection, even if this parameter is set to 1. Set to "0"
and ensure each motor has a thermal relay installed.
Sets the motor thermal overload protection (OL1) time.
Refer to V1000 Technical Manual for details.
Refer to V1000 Technical Manual for details.
Refer to V1000 Technical Manual for details.
Refer to V1000 Technical Manual for details.
L2: Momentary Power Loss
0: Disabled - Drive trips on (UV1) fault when power is lost.
1: Power Loss Ride-Thru Time - Drive will restart if power returns
within the time set in L2-02.
2: CPU Power Active - Drive will restart if power returns as long as the
CPU is working.
Refer to V1000 Technical Manual for details.
Refer to V1000 Technical Manual for details.
Refer to V1000 Technical Manual for details.