H1-
Function
Setting
66
KEB Ride-Thru 1 (N.O.)
67
Communications Test Mode
68
High-Slip Braking
6A
Drive Enable
75
Up 2 Command
76
Down 2 Command
7A
KEB Ride-Thru 2 (N.C.)
7B
KEB Ride-Thru 2 (N.O.)
7C
Short-Circuit Braking (N.O.)
7D
Short-Circuit Braking (N.C.)
7E
Forward/Reverse Detection
9F
DriveWorksEZ enable
No.
Use H2 parameters to assign functions to the multi-function digital outputs.
H2-01 Terminal MA, MB and MC Function Selection (relay)
H2-02 Terminal P1 Function Selection (open-collector)
H2-03 Terminal P2 Function Selection (open-collector)
H2-06 Watt Hour Output Unit Selection
H2-
Function
Setting
0
During Run
1
Zero Speed
2
Fref/Fout Agree 1
3
Fref/Fset Agree 1
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
H1 Multi-Function Digital Input Selections
Open: Normal operation
Closed: KEB Ride-Thru 1 enabled
Tests the MEMOBUS/Modbus RS-485/422 interface.
Closed: High-Slip braking is executed. Drive stops.
Open: Drive disabled. If this input is opened during run, then the drive
will stop as specified by parameter b1-03.
Closed: Ready for operation.
Open: Maintains the current frequency reference
Closed: Increases or decreases the frequency reference.
Open: KEB Ride-Thru 2 enabled
Closed: Normal operation
Open: Normal operation
Closed: KEB Ride-Thru 2 enabled
Open: Normal operation
Closed: Short-Circuit Braking
Direction of rotation detection (for Simple V/f w/PG)
Open: DWEZ enabled
Closed: DWEZ disabled
Name
H2: Multi-Function Digital Outputs
H2 Multi-Function Digital Output Settings
Closed: A Run command is active or voltage is output.
Closed: Output frequency is 0.
Closed: Output frequency equals the speed reference (plus or minus the
hysteresis set to L4-02).
Closed: Output frequency and speed reference equal the value in L4-01
(plus or minus the hysteresis of L4-02).
7.1 Parameter Table
Description
Description
Refer to "Multi-Function Digital
Output Selection Table" for a
description of setting values.
Refer to V1000 Tech Manual.
Description
Range
7
0 to 192
0 to 4
127

Advertisement

Table of Contents
loading

Table of Contents