YASKAWA V1000 Quick Start Manual page 125

Compact vector control drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

H1-
Function
Setting
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (OH2)
C
Terminal A2 Enable
F
Not used
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast-Stop (N.O.)
16
Motor 2 Selection
17
Fast-stop (N.C.)
18
Timer Input Function
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Program Lockout
1E
Reference Sample Hold
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
H1 Multi-Function Digital Input Selections
Used to select Multi-Step Speeds set in d1-01 to d1-16
Open: Selected speed reference
Closed: Jog Frequency reference (d1-17). Jog has priority over all other
reference sources.
Used to switch between Accel/Decel. Time 1/2
Open: Normal operation
Closed: No drive output
Open: No drive output
Closed: Normal operation
Closed: The drive pauses during acceleration or deceleration and
maintains the output frequency.
Closed: Displays an OH2 alarm
Open: Terminal A2 disabled
Closed: Terminal A2 enabled
Select this setting when not using the terminal or when using the terminal
in a pass-through mode.
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency reference
Closed: Runs forward at the Jog Frequency d1-17.
Closed: Runs reverse at the Jog Frequency d1-17.
Closed: Resets faults if cause is cleared and Run command removed.
Closed: Decelerates at the Fast-Stop time C1-09.
Open: Motor 1 (E1-
Closed: Motor 2 (E3-
Open: Decelerates according to C1-09 (Fast-stop Time)
Set the timer delay using parameters b4-01 and b4-02.
Closed: PID control disabled
Switches Accel/Decel times.
Open: Parameters can not be edited. (except U1-01 if reference source is
set for operator)
Closed: Parameters may be edited and saved.
Closed: Samples the analog frequency reference and operates the drive at
that speed.
7.1 Parameter Table