8.2 UL Standards
Wire Gauge
Terminal
mm
(AWG
Screws
2
M3.5
2
(14)
3.5/5.5
(12/10)
8
(8)
14
(6)
22
(4)
30/38
(3/2)
<1> Use the specified crimp terminals (Model 14-NK5) when using CIMR-V 2A0030, V 2A0040, V 4A0023
with 14 mm
2
(6 AWG).
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should
have a continuous maximum allowable temperature of 75°C 600 Vac UL-approved vinyl-
sheathed insulation.
Drive Model CIMR-V
BA0001
BA0002
BA0003
BA0006
BA0010
BA0012
2A0001
152
Crimp Terminal
Model Numbers
R2-3.5
M4
R2-4
M5
R2-5
M6
R2-6
M4
R5.5-4
M5
R5.5-5
M6
R5.5-6
M8
R5.5-8
M5
R8-5
M6
R8-6
M8
R8-8
M5
R14-5
M6
R14-6
M8
R14-8
M6
R22-6
M8
R22-8
M8
R38-8
Table 8.5 Recommended Input Fuse Selection
200 V Class Single-Phase Drives
200 V Class Three-Phase Drives
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
Time Delay/
Class RK5 Fuses
600 Vac, 200 kAIR
TRS5R
TRS10R
TRS20R
TRS35R
TRS50R
TRS60R
TRS5R
Tightening Torque
N m (lb to in.)
0.8 to 1.0 (7.1 to 8.9)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
9.0 to 11.0 (79.7 to 97.4)
Fuse Ampere Rating
5
10
20
35
50
60
5