4.6 Test Run
Auto-Tuning Fault Codes
Calculation of abnormal measurements or pressing
interrupt Auto-Tuning.
Figure 4.11
A – Normal Auto-Tuning Display
Performing Auto-Tuning
The following example illustrates how to perform Rotational Auto-Tuning.
Note: The following example is shown with the drive in Open Loop Vector Control
(A1-02 = 2).
Selecting the Type of Auto-Tuning
1.
Turn on the power to the drive. The initial display appears.
Press the
key until the Auto-Tuning screen appears.
2.
3.
Press
to begin setting parameters.
Press
to display the value for T1-01.
4.
5.
Press
to select the digit to edit.
6.
Press
and set the drive to perform Rotational Auto-Tuning
(00).
Save the setting by pressing
7.
8.
The display automatically returns to the screen shown in Step 3.
76
A
Figure 4.11 Auto-Tuning Interruption Display
Step
.
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
before completion will
STOP
B
B – Auto-Tuning Interrupted
Display/Result