7.1 Parameter Table
No.
H3-09
Terminal A2 Signal Level Selection
H3-10
Terminal A2 Function Selection
H3-11
Terminal A2 Gain Setting
H3-12
Terminal A2 Input Bias
H3-13
Analog Input Filter Time Constant
H3-
Setting
0
Frequency Bias
1
Frequency Gain
2
Auxiliary Frequency Reference (used as multi-step speed 2)
4
Output Voltage Bias
7
Overtorque/Undertorque Detection Level
B
PID Feedback
C
PID Set Point
E
Motor Temperature (PTC input)
F
Not used / Pass-through mode
10
FWD Torque Limit
11
REV Torque Limit
12
Regenerative Torque Limit
15
FWD/REV Torque Limit
16
Differential PID Feedback
No.
Use H4 parameters to configure the multi-function analog output terminals.
Multi-Function Analog Output
H4-01
Terminal AM)
130
Name
H3 Multi-Function Analog Input Settings
Function
Name
H4: Multi-Function Analog Outputs
Selects data output via multi-function analog output terminal AM.
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
Sets the input signal level for terminal A2.
0: 0 to +10 V (with lower limit)
1: 0 to +10 V (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA
Sets the function of terminal A2.
Sets the level of the input value selected in H3-10 when 10 V (20
mA) is input at terminal A2.
Sets the level of the input value selected in H3-10 when 0 V (0 or 4
mA) is input at terminal A2.
Sets the primary delay filter time constant for terminals A1 and A2.
Used for noise filtering.
Description
Maximum Input Level Possible
Max output frequency (E1-04).
Frequency reference (voltage)
Max output frequency (E1-04)
Motor rated voltage (E1-05).
Open Loop Vector: Motor rated torque
V/f control: Drive rated current
10V = 100%
10V = 100%
10 V = 100.00%
Motor rated torque
Motor rated torque
Motor rated torque
Motor rated torque
10 V = 100%
Description