7.1 Parameter Table
No.
Name
d1-07 Frequency Reference 7
d1-08 Frequency Reference 8
d1-09 Frequency Reference 9
d1-10 Frequency Reference 10
d1-11 Frequency Reference 11
d1-13 Frequency Reference 13
d1-14 Frequency Reference 14
d1-15 Frequency Reference 15
d1-16 Frequency Reference 16
d1-17 Jog Frequency Reference
d2-01 Frequency Reference Upper Limit
d2-02 Frequency Reference Lower Limit
Master Speed Reference Lower
d2-03
Limit
d3-01 Jump Frequency 1
d3-02 Jump Frequency 2
d3-03 Jump Frequency 3
d3-04 Jump Frequency Width
Use d4 parameters to configure the drive frequency reference hold function.
Frequency Reference Hold Function
d4-01
Selection
Frequency Reference Bias Step (Up/
d4-03
Down 2)
120
Frequency reference when digital inputs "Multi-Step Speed
Reference 2, 3" (H1-
Frequency reference when multi-function input "Multi-Step speed
reference 1, 2, 3" (H1-
Frequency reference when multi-function input "Multi-Step Speed
Reference 4" (H1-
Frequency reference when digital input "Multi-Step Speed Reference
1, 4" (H1-
Frequency reference when digital inputs "Multi-Step Speed
Reference 2, 4" (H1-
Frequency reference when digital inputs "Multi-Step Speed
Reference 3, 4" (H1-
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 3, 4" (H1-
Frequency reference when digtial inputs "Multi-Step Speed
Reference 2, 3, 4" (H1-
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 2, 3, 4" (H1-
Frequency reference when digital inputs "Jog Frequency Reference",
"Forward Jog" or "Reverse Jog." are on.
d2: Frequency Upper and Lower Limits
Use d2 parameters to configure the frequency reference limits.
Sets the frequency reference upper limit as a percentage of maximum
output frequency (E1-04).
Sets the frequency reference lower limit as a percentage of maximum
output frequency (E1-04).
Refer to V1000 Technical Manual for details.
d3: Jump Frequency
Use d3 parameters to configure the drive Jump Frequency settings.
d3-01 to d3-04 allow programming of three prohibited frequency
reference points for eliminating problems with resonant vibration of
the motor / machine.
This parameter sets the dead-band width around each selected
prohibited frequency reference point.
d4: Frequency Reference Hold
0: Disabled
1: Enabled
Sets the bias added to the frequency reference when the Up/Down 2
digital inputs are set.
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide
Description
= 4 and 5) are on.
= 3, 4, 5) are on.
= 32) is on.
= 3 and 32) are on.
= 4 and 32) are on.
= 5 and 32) are on.
= 3, 5, 32) are on.
= 4, 5, 32) are on.
= 3, 4, 5, 32) are on.