<2> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps
should be equal to or greater than the motor rated current.
<3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and
power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<7> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND)ratings for the drive
include rated input and output current, overload capacity, carrier frequency, current limit, and
maximum output frequency. Set parameter C6-01 to "0" for HD ratings or "2" for ND ratings.
Default is ND (C6-01 = 1).
YASKAWA ELECTRIC TOEP C710606 14A YASKAWA AC Drive - V1000 Quick Start Guide