CV3100 series and MINI series high performance general purpose inverter instruction manual
Note:
1. The 18, 19 items are only available to terminal DI6, i.e. terminal DI6 can be defined
as these functions.
2.The max frequency of input pulse is 20 KHz; low amplitude level is 0V, the high is
18~26V.
20:Exterior reset signal input (RESET)
When the inverter is in failure, it can clear the failures and resume the inverter to
normal status, which function is equal to the function of key STOP/RESET.
21:UP/DOWN terminal frequency reset
When the frequency setting channel selection is available to terminal UP/DOWN
control,it can clear the incremental changes of terminal UP/DOWN
22:PID operation available
When the terminal is defined as this function under terminal control mode, it can make
PID operation in effect.
23:Programmable multi-step speed running available
When the terminal is defined as this function under terminal control mode, it can make
programmable multi-step speed running(PLC) in effect.
24:Wobbling frequency operation available selection
When the terminal is defined as this function under terminal control mode, it can make
wobbling frequency operation in effect.
25:Wobbling freq. status reset
When the wobbling frequency function is selected, whether it is automatically or
manually input by terminals, closure of the terminal defined as this function will
remove memory-status information of wobbling frequency, which will restart if
disconnection of the terminal.
26:Exterior stop command
This command is available to all running command channels. If this terminal function
is available, the inverter will be stopped basing on mode defined by P2.11
27:Free stop control
Used for stopping the inverter under external terminal control mode. When the
terminal defined as this function with common terminal COM is closed, the inverter
will stop. If they are open, it will start to run by speed tracking mode.
28:Inverter accel. & decel. forbidden command
If this terminal function is available, it can prevent the inverter from influence by extra
6-29