EasyDrive CV3100 Series Instruction Manual page 87

High performance general purpose inverter
Table of Contents

Advertisement

CV3100 series and MINI series high performance general purpose inverter instruction manual
shown as t1 in Diagram 6-8.
Diagram 6-8 forward and reverser rotation dead-zone interval
Notice: there still has dead-zone interval after the former forward stopping and
before the next reverse starting
P2.11
Stop mode
Setting range
0:Ramp to stop
The inverter frequency output decelerates in the time specified by P0.15, down to zero
and then the inverter turns off.
If the DC brake function is selected for stop, when the output frequency decrease
down to DC brake starting frequency, the inverter will start DC brake until completely
stopping output.
1:Coast to stop
When the inverter receives stop command, it stops output immediately and the motor
will run freely to stop. In general ,when you choose this way to achieve stop quickly ,it
need to match up external mechanical brake .
It is inhibitive to be used for pump loads, or it may lead to water hammer effect and
Output
frequency
t1
0
1
time
Factory setting
Ramp to stop
Coast to stop
6-19
0