CV3100 series and MINI series high performance general purpose inverter instruction manual
Fault
Fault name
code
Er09
Module fault
Er10
Over heat
(Er19)
radiator
Overload of
Er11
inverter
Overload of
Er12
motor
Fault of
Er13
peripheral
equipment
Fault of serial
Er14
port
communication
Er15
Reserved
Incorrect
Er16
current
detection
Fault of
communication
Er17
between
keyboard and
control panel
Er18
CPU fault
Possible cause
① Inverter outputs short circuit or
earthing.
② Instant over current of inverter
③Too high environment temperature
④Air flue is blocked or fan is
damaged
⑤DC auxiliary power supply occurs
fault
⑥ Abnormal controlpanel
① Too high environment temperature
② Fan is damaged
③ Flue is blocked
① Too high torque boost or unsuitable
V/F curve
② Too short accelerating time
③ Too large load
①Too high torque boost or unsuitable
V/F curve
② Too low main voltage
③Locked rotor of motor or too large
abrupt change of load
④Incorrect setting of motor overload
protection factor
①Fault input terminal of peripheral
equipment is close
① Improper setting of baud rate
② False of serial port communication
③ Without upper machine
communication signal
① The current detecting device is
damaged or the circuit occurs fault
②DC auxiliary power is damaged
①The circuit connecting keyboard
and control panel occurs fault
② The terminal is poor in connecting
--
7-3
Solution
① Examine the connecting
wire;
② Refer to solution against over
current
③Clean the air flue or change
the fan;
④Ask for service from
manufacturer or agency.
① Lower environment
temperature
② Change the fan
③ Clean the flue and change
the ventilation condition;
①Reduce the torque boost and
adjust the V/F curve.
② Extend accelerating time
③Reduce load or choose the
inverter of large power
① Reduce the torque boost
value or adjust the V/F curve.
② Examine main voltage
③ Examine load
④Set the motor overload
protection factor correctly
①Disconnect the terminal input
and remove the fault.
① Set baud rate correctly
②Examine communication
cable and ask for service
③Check whether PC works and
the connection is correct.
①Ask for service from
manufacturer or agency.
②Ask for service from
manufacturer or agency.
① Ask for service
② Examine and reconnect
--