EasyDrive CV3100 Series Instruction Manual page 143

High performance general purpose inverter
Table of Contents

Advertisement

CV3100 series and MINI series high performance general purpose inverter instruction manual
Query the frame:01H+06H+00H+06H+13H+88H+64H+9DH
Specific meaning is as follows:
Address:01H---- this device ID is 01H.
Function:06H ---- Function code
Data address: 0006H ----register address is 0x0006, indicates write content
into address 0x0006 register.
Data content:1388H ----the write content,write in 1388H in address
0x0006 register.
CRC CHK:Reference to the last page for methods to get RTU mode check
code (CRC Check).
Response the frame:01H+06H+00H+06H+13H+88H+64H+9DH
Specific meaning is as follows:
Address:01H
Function:06H ----Function code
data address: 0006H ----register address is 0x0006, indicates write data into
register
Data content:1388H----indicates the content of writing into register
CRC CHK:Reference to the last page for methods to get RTU mode check
code (CRC Check).
10H : Write many data continuously ( only revise 2 parameters
continuously)
Preset data into every register in order,when broadcast,this function can
preset data into the same address of all slave machine.
Query message frame format:
Slave address+10H+register the first address+register number+data byte
number+the first data content+the second data content+ CRC CHK
---- this device ID is 01H。
9-9