EasyDrive CV3100 Series Instruction Manual page 84

High performance general purpose inverter
Table of Contents

Advertisement

CV3100 series and MINI series high performance general purpose inverter instruction manual
frequency
P2.01
startup
Diagram 6-6 Start and stop frequency output curve
P2.03
DC braking current level at starting
Setting range
DC braking time at starting
P2.04
Setting range
DC braking current level at starting:Brake current percent when the inverter starts
according to DC brake.
DC braking time at starting:DC brake current output duration during the inverter
starts.
When DC braking time is 0, the function is invalid; when P2.03, P2.04 are set, the
motor will execute DC brake function first, second start from starting frequency
lasting for the time defined by P2.02, and then accelerate to requested frequency.
Note:Only when P0.00=1,this group parameters are valid.
P2.05
Accel.&Decel. way
Setting range
0:Beeline acceleration
The inverter frequency output vary by fixed speed, which is linear relationship with
accel & decel time.The most of loads use this way.
1:S-curve acceleration or deceleration
During accelerating or decelerating, the inverter frequency output is S-curve
relationship with accel & decel. time, shown as Diagram 6-7. This function is for
P2.02
0—100.0%
0.0—30.0s
0
Beeline
1
S-curve
6-16
Stop per deceleration
Without DC braker
Free running to stop
time
Factory setting
Factory setting
Factory setting
0.0%
0.0s
0