CV3100 series and MINI series high performance general purpose inverter instruction manual
P5.16
Combination given arithmetic setting
Setting range
LED single digit:Arithmetic 1
0:Addition
1:Subtraction
2:Absolute value(subtraction)
3:Choose Maximum.
4:Choose Minimum.
LED tens digit:Arithmetic 2
0:Addition
1:Subtraction
2:Absolute value(Subtraction)
3:Choose Maximum.
4:Choose Minimum.
5:Operand 3 not be concerned with operation
LED Hundreds & thousands digit: Reserved
Note: only P0.01=7,parameter P5.15、P5.16 are effective.
When P0.01=7, each analog and digital input quantity compounding arithmetic
formula as below:
If P5.16 LED tens digit is set to ―5‖,operand 3 will not participate in the arithmetic,
and only the other two operands 1 and 2 are in operation compounding.
For example first, if P5.15 is set to ―531‖ and P5.16 is set to ―10‖, the operation
compounding is equal to {(digital setting 1+ communication setting)-AI2}
For example second, if P5.15 is set to value ―410‖ and P5.16 is set to ―21‖, the
operation compounding is equal to {(keypad potentiometer – digital setting)-AI1}.
Note:
Algorithm 1: Under any circumstances, the operation process is operating operand 1
and operand 2 according to algorithm 1 to get result 1, then operating result 1 and
operand 3 to get the final result. If operation result 1 of the former two operands is
negative, the negative is defaulted to 0.
Algorithm 2:If the operation result is always negative, moreover algorithm 2 is not
absolute value operation, system will default the result to 0.
00—54
6-41
Factory setting
00