EasyDrive CV3100 Series Instruction Manual page 93

High performance general purpose inverter
Table of Contents

Advertisement

CV3100 series and MINI series high performance general purpose inverter instruction manual
2:Eliminate fault record
It will eliminate historical records of inverter.
P3.02
Parameter read-in protection
Setting range
0:Allowed to modify all parameters
Note:Some of the parameters can not be changed during inverter running.
1:Only allow to change the frequency
2:Forbidden to modify all parameters
This function can prevent others from arbitrarily modifying the parameters setting of
inverter.
P3.03
Factory password
Setting range
P3.04
Monitoring parameter 1 selection
Setting range
P3.05
Monitoring parameter 2 selection
Setting range
These parameters are sued for display objects on the display panel, i.e. contents display
on LED or LCD. Hereinto, LED displays monitoring parameter 1. LCD displays
monitoring parameter 2 on its down left corner region.
P3.06
Linear velocity quotiety
Setting range
When the velocity display is linear velocity, the converting formula shows as below:
Linear velocity = Frequency × Linear velocity quotiety
P3.07
Close loop display quotiety
Setting range
PID feedback value ÷ the setting value = Close loop display quotiety × Actual
feedback value ÷ the setting value
P3.08
Software edition
Setting range
0
Allowed to modify all parameters
1
Only allow to change the frequency
2
Forbidden to modify all parameters
0—9999
0—18
0—18
0.01—100.0
0.01—100.0
0—99.99
6-25
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Factory Setting
0
0
0
1
1.00
1.00