CV3100 series and MINI series high performance general purpose inverter instruction manual
machine.
Host machine send(hexadecimal):01 03 00 03 00 01 74 0A
Slave machine response(hexadecimal):01 03 02 13 88 B5 12
Known from response massage,P0.03 value is 1388H(hexadecimal),decimal is
5000,because has two decimal point,response frequency is 50.00HZ
② Read the monitoring parameter
Parameter address refer to table 1.
For example:read D-07 busbar voltage monitoring parameter value from
address 01H slave machine.
Host machine send(hexadecimal):01 03 0D 07 00 01 37 67
Slave machine response(hexadecimal):01 03 02 01 DB F9 8F
Known from response massage,D-07 value is 1DBH(hexadecimal),decimal is
475,Indicates the measured busbar voltage is 475v, which is same with the value of
keyboard D-07
③ Read running status massage(address is 0E00H)
For example:read running status massage from address 01H slave machine.
Host machine send(hexadecimal):01 03 0E 00 00 01 86 E2
If slave machine response(hexadecimal):01 03 02 00 21 78 5C
From feedback massage is 0021H,binary system is:
0 0000000
|
|
|
|
|
|
|
|_________________________________ Bit15:0 no fault happen
0 0 1 0 0 0 0 1 ——> 0001H(hexadecimal)
| | | | | |
| | | | | |_______ Bit2:0 output phase order is forward
| | | | |__________ Bit3:0 command direction is forward
| | | |_____________ Bit4:0 stop state
| | |________________ Bit5:1 frequency channel is 1
| |___________________ Bit6:0 not acceleration state
|______________________ Bit7:0 not deceleration state
|__ Bit0:1 voltage normal