EasyDrive CV3100 Series Instruction Manual page 122

High performance general purpose inverter
Table of Contents

Advertisement

CV3100 series and MINI series high performance general purpose inverter instruction manual
This parameter define the wobbling frequency running time from its lower limit
frequency to upper limit frequency, namely acceleration time of wobbling period.
Actual triangle wave risetime = Wobbling frequency period × P7.17
P7.18
Norm of central wobbling freq.
Setting range
It is the normal value of central output frequency of the inverter.
Actual wobbling center frequency is the accumulated value of this parameter value
and the setting frequen from external frequency setting passage P0.01.
Actual wobbling center frequency = 【P7.18】 + Frequency set by the channel which
is specified by P0.01.
Note:Wobbling operating frequency is restricted by the upper and lower limit
frequency. Incorrect setting will lead to abnormal running of wobbling frequency.
Wobbling
center freq
Wobbling
presetting
frequency
Note:
Priority to frequency setting as below:
Jog operating frequency > Wobbling frequency operating frequency >PID provision
operating frequency > Programmable multi-step speed operating frequency >
Multi-function terminal selection frequency > frequency setting channel selection.
0.00—Maximum frequency
Wobbling
freq width
Wobbling
freq width
T1
T2
Diagram 6-29 Wobbling frequency setting
Factory setting
Skip freq
T3
6-54
10.00Hz