CV3100 series and MINI series high performance general purpose inverter instruction manual
parameter at the same time.
definition
Command
for drive
Command content synthesis example:
① Continuous running start command in forward direction
0000000000 01 11 10 ——> 001EH(hexadecimal)
② Stop command:
0000000000 00 00 01 ——> 0001H(hexadecimal)
●Each function code application example:
Note:the data sent from host machine and slave machine are hexadecimal
number.
(1) 03H function code application
① read the set parameter
Parameter address refer to table1.
For example:read the set parameter value of P0.03 frequency from address 01H slave
Table4、commonly used command example
Parameter address
(hexadecimal)
2000H
|
|
|______ Bit0~1: 10 start
|
|__________ Bit2~3: 11 continuous running
|______________ Bit4~5: 01 forward direction command
|
|
|______ Bit0~1: 01 stop
|
|__________ Bit2~3: 00 Non-function
|______________ Bit4~5: 00 Non-function
Data content
001EH:Forward run
002EH:Reverse run
0013H:Forward jog
0023H:Reverse jog
0001H:Stop
0031H:Fault reset
9-15