6.8 Programmable running parameter
P7.00
Programmable running control
Setting range
LED single digit:Running mode selection
0:No action
1:Single circulation(Simple PLC)
2:Continuous circulation(Simple PLC)
3:Holding ultimate value after single circulation(Simple PLC)
4:Wobbling frequency running
LED tens digit:Programmable multi-step speed (PLC)running availability
selection
0:Automatic availability
1:Manual availability by defining of multi-function terminal
LED Hundreds digit: Wobbling frequency running availability mode
0:Automatic availability
1:Manual availability by defining multi-function terminal.
LED thousands digit: Reserved
Detailed function explanation as below:
0:No action
Programmable multi-step speed running is invalid.
1:Single circulation
The inverter will stop automatically after single circulation, startup of which asks for
running command input. If the running time of some stage is zero, it will jump this
stage to enter into next stage when running, details shown as Diagram 6-26:
a1
T1
RUN
000-114
f2
a2
f1
d3
a3 f3
d5
a4
f4
T3
T2
T4
Diagram 6-26 Single circulation running
f6
d7 f7
a6
f5
d7
a5
T7
T5
T6
6-49
Factory setting
000