CV3100 series and MINI series high performance general purpose inverter instruction manual
Can know slave machine voltage is normal, phase-order direction is forward,command
direction is forward,stop state ,frequency given mode is digit given 1.
If slave machine response(hexadecimal):01 03 02 93 21 14 AC
From feedback massage is 9321H,binary system is:
1 0010011
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|________________________ Bit8~14:0010011 fault No. is 19
|_________________________________ Bit15:1 happen fault
Can known slave happen Er-19 fault;Low 8-bit 21H is state massage, the
meaning same with above.
(2) 06H function code application
① Write the set parameter
Parameter address refer to table 1.
For example, Change the parameter P0.03 of address 01H slave machine to
1088H,decimal is 4232, namely 42.32HZ .
Host machine send(hexadecimal):01 06 00 03 10 88 74 6C
Slave machine response(hexadecimal):01 06 00 03 10 88 74 6C
Response information consistently show successful updated,the others parameter is
also like this.
② Write Command Parameter
For example:Write in forward direction continuous running command to the
address 01H slave machine(001EH)
0 0 1 0 0 0 0 1 ——> 0001H(hexadecimal)
| | | | | |
| | | | | |_______ Bit2:0 output phase-order is forward
| | | | |__________ Bit3:0 command direction is forward
| | | |_____________ Bit4:0 stop state
| | |________________ Bit5:1 frequency channel 1
| |___________________ Bit6:0 not a acceleration state
|______________________ Bit7:0 not deceleration state
|__ Bit0:1 voltage normal
9-17